BGH2UNCTRLHT-01 Universal Hot Surface Ignition Control Installation Instructions 9
Setup and Adjustments
Select Dip Switch Positions
A 5 position dip switch is provided on the controller to
allow for field programming of 1 to 32 possible pre-
defined sets of timing sequences. Select a predefined
timing sequence from Table 1 and then set the dip
switches on the control.
To change the settings, remove power from the circuit
board, change settings and re-apply power to the
circuit board.
The dip switches remain active until 10 consecutive
power cycles occur without a change in any dip switch
setting. Once this occurs, dip switches become
inactive and cannot further be used to change timing
specifications.
Table 2: BGHUNCNTRLHT-01 Universal HSIC
Parameters/Dip Switch Positions
5 Position Dip
Switch Settings
HSIC Parameters
*Warmup
Pre-
Purge
Between
Purge
Ignition
Trial Time
No. of
Trials
ON OFF
(Sec.) (Sec.) (Sec.) (Sec.) #
None 1,2,3,4,5 45 30 90 7 3
5 1,2,3,4 17 30 90 7 3
4 1,2,3,5 45 17 77 7 3
4,5 1,2,3 17 17 77 7 3
3 1,2,4,5 45 None 60 7 3
3,5 1,2,4 17 None 60 7 3
3,4 1,2,5 34 32 96 7 3
3,4,5 1,2 34 None None 7 3
2 1,3,4,5 45 30 None 7 1
2,5 1,3,4 17 30 None 7 1
2,4 1,3,5 45 17 None 7 1
2,4,5 1,3 17 17 None 7 1
2,3 1,4,5 45 None None 7 1
2,3,5 1,4 17 None None 7 1
2,3,4 1,5 34 32 None 7 1
2,3,4,5 1 34 None None 7 1
1 2,3,4,5 45 30 90 4 3
1,5 2,3,4 17 30 90 4 3
1,4 2,3,5 45 17 77 4 3
1,4,5 2,3 17 17 77 4 3
1,3 2,4,5 45 0 60 4 3
1,3,5 2,4 17 0 60 4 3
1,3,4 2,5 34 32 96 4 3
1,3,4,5 2 34 0 0 4 3
1,2 3,4,5 45 30 None 4 1
1,2,5 3,4 17 30 0 4 1
1,2,4 3,5 45 17 0 4 1
1,2,4,5 3 17 17 0 4 1
1,2,3 4,5 45 0 0 4 1
1,2,3,5 4 17 0 0 4 1
1,2,3,4 5 34 32 0 4 1
1,2,3,4,5 None 34 0 0 4 1
1
2
3
4
5
ON
OFF
Figure 3: 5 Position
Dip Switch
Switch settings shown
with all 5 switches in the
OFF positions.
*Warmup time is timed ignition.